SPECIALTY
Low-carbon Intelligent Fire Fighting Equipment And Solutions
/
/
/
Electric fire intelligent monitor
电气火灾智能监测仪2
电气火灾智能监测仪1
  • Electric fire intelligent monitor

  • The electrical fire intelligent monitoring system is divided into two types: the first type is bus type, including electrical fire monitoring host and electrical fire intelligent monitor. The electrical fire monitoring host can collect the electrical fire intelligent monitor on the bus in real time to detect the protected electrical The leakage, temperature, arc, overload and other values of the equipment output alarm information according to the set upper and lower thresholds, and support local display, analysis, storage, alarm and linkage functions; the other type is an independent electrical fire intelligent detector , Built-in wireless communication module, can upload the alarm information monitored by the electrical fire intelligent detector to the cloud platform, and support local display, analysis, storage, alarm and linkage functions.
  • 电气火灾智能监测仪2
    电气火灾智能监测仪1
产品详情
企业下载

电气火灾智能监测仪1Product introduction

The electrical fire intelligent monitoring system is divided into two types: one is the bus type, including electrical fire Monitoring host and electrical fire intelligent monitor, the electrical fire monitoring host can collect the electrical fire intelligent monitor on the bus in real time to monitor the leakage, temperature, arc, overload and other values of the protected electrical equipment, and output according to the set upper and lower thresholds Alarm information supports local display, analysis, storage, alarm and linkage functions; the other is a stand-alone electrical fire intelligent detector with a built-in wireless communication module, which can upload the alarm information monitored by the electrical fire intelligent detector to Cloud platform, and supports local display, analysis, storage, alarm and linkage functions.

Related parameters

Type Bus type Freestanding
Rated working voltage DC 24V AC220V/50Hz
Rated working current ≤5mA ≤50mA
Communication method TBuS-YC NB-loT
Work mode Real-time measurement Real-time upload
Collection period Real time
Upload cycle Real time
Alarm period Real time
Measuring range 100 ~999mA 55℃~140℃
Alarm threshold Set Constant value
Working temperature - 20°C~60°℃
Installation method site Installation (rail)

 

Related Products

Previous page
1